Horizontal Sidewall Sprinklers

Horizontal Sidewall Sprinklers

Description

Horizontal sidewall sprinklers are generally used in lieu of pendent and upright sprinklers because of building construction or installation economy considerations. They are designed for installation along a wall or the side of a beam and just beneath a smooth ceiling. Installed with their centerline of waterway horizontal, these sprinklers produce a quarter‐spherical water discharge pattern that is predominately directed downward and outward from the deflec or; however, a portion of the spray is also directed towards the back wall.

Model BF007/BF008, Standard / Quick Response Horizontal Side- wall Sprinklers (Ref. Figure A), are automatic sprinklers of the frangible bulb type, and standard spray, 1/2” orifice, 5 / 3 mm bulb. They are “standard / quick response ‐ standard orifice sidewall sprinklers” intended for use in fire sprinkler systems designed in accordance with the standard installation rules recognized by the ap- plicable Listing or Approval agency (e.g., UL Listing is based on NFPA 13 requirements)

Sprinkler Operation

During a fire conditions, the thermal‐sensitive liquid in the glass bulb expands, causing the bulb to shatter, releasing the button and spring seal assembly. Water flowing through the sprinkler ori- fice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.

Coverage

For coverage area and sprinkler placement, refer to NFPA13 standards.

Sprinkler Materials

Frame ………………………… Brass Casting DZR Deflector……………………… Brass UNS-28000
Glass Bulb…………………….. Glass with Glycerin Solution
JOB® G5 for BF007
JOB® F3 for BF008 Set Screw……………………… Brass UNS-28000 Button………………………….. Brass UNS-62300
Spring…………………………… Stainless Steel Seal……………………………… Teflon Tape Standard Escutcheon………… Cold Rolled Steel